GDPD-316M Handheld Partial Discharge Inspection Tester
GDPD-316M Digital Intelligent Handheld Partial Discharge Inspection Tester with TEV/AE/UHF/HFCT Multi-Sensor Integration, Built-in Expert Diagnosis System, RFID Equipment Identification, Multiple Synchronization Modes, for 10kV-500kV Power Equipment Live Partial Discharge Detection.
- Description
- Specifications
- Applications
- Advantages
- FAQ
- Recommended Products
Description
The GDPD-316M is a professional, field-optimized comprehensive handheld partial discharge inspection instrumentexclusively designed for live detection and condition assessment of high-voltage power equipment. It fully complies with DL/T 1432.3-2016, DL/T 1982-2019 and IEC 60270:2015 standards, integrating four mainstream partial discharge detection methods into one unit, which can flexibly configure different sensors according to the type of equipment under test.
The instrument adopts advanced high-speed digital signal processing technology and intelligent anti-interference algorithms, which can effectively suppress on-site electromagnetic interference and accurately extract weak partial discharge signals. Its built-in expert diagnosis system can automatically analyze test data, judge discharge type and severity, and provide maintenance suggestions. Equipped with a 4.3-inch high-resolution color touch screen and intuitive graphical interface, it supports multiple map displays including PRPD, PRPS, time-domain waveform and spectrum. With RFID equipment identification function and WIFI/BT wireless communication, it can realize intelligent inspection management and data cloud upload. The host weighs only 0.45kg and supports one-hand operation, making it ideal for all-day on-site inspections. Ideal for daily inspection, defect detection, fault location and condition assessment of switchgears, ring main units, GIS, power transformers, high-voltage cables, instrument transformers and other power equipment.
Specifications
| Parameter | Specification |
|---|---|
| TEV Detection | |
| Frequency Range | 500kHz – 50MHz |
| Measurement Range | 0 – 80dBmV |
| Accuracy | ±1dB |
| Resolution | 1dBmV |
| AE Detection | |
| Contact Ultrasonic Frequency | 20kHz – 300kHz |
| Non-Contact Ultrasonic Peak Frequency | 40kHz |
| Sensitivity | 0.1mV |
| Measurement Range | 0.1mV – 1V |
| UHF Detection (Optional) | |
| Frequency Range | 300MHz – 1500MHz |
| Measurement Range | 0 – 70dB |
| Accuracy | ±1dB |
| HFCT Detection (Optional) | |
| Frequency Range | 500kHz – 50MHz |
| Transmission Impedance | >10mV/mA (10MHz) |
| Dynamic Range | 0 – 80dB |
| System Parameters | |
| Synchronization Modes | Internal synchronization, Power synchronization, Optical synchronization (optional) |
| Display | 4.3-inch high-brightness color touch screen |
| Storage | 8G large-capacity storage |
| Communication | WIFI, Bluetooth, Type-C USB |
| RFID | Built-in RFID reader |
| Headphone Output | 3.5mm stereo headphone jack |
| Language Support | Chinese/English bilingual |
| Power Supply | Built-in rechargeable lithium battery |
| Battery Life | ≥8 hours continuous operation |
| Charging Mode | Type-C interface, 5V/2A |
| Charging Time | ≤5 hours (full charge) |
| Dimensions | 181×107×36mm (L×W×H) |
| Weight | ~0.45kg (including battery) |
| Operating Temperature | -20℃ ~ +60℃ |
| Operating Humidity | 0 – 90% RH (non-condensing) |
| Altitude | ≤2000m |
| Compliance | DL/T 1432.3-2016, DL/T 1982-2019, IEC 60270:2015, GB/T 7354-2018 |
Applications
Core Test Objects
- Switchgears & ring main units: 10kV-35kV indoor/outdoor switchgears and ring main units
- GIS equipment: 110kV-500kV GIS and HGIS gas insulated switchgears
- Power transformers: 10kV-500kV oil-immersed and dry-type power transformers
- High-voltage cables: 10kV-220kV XLPE power cables and cable terminals
- Instrument transformers: 10kV-220kV current transformers (CT) and voltage transformers (VT)
- Other equipment: Reactors, surge arresters, overhead lines
Typical Usage Scenarios
- Power companies: Substation daily inspection and preventive maintenance
- Defect diagnosis teams: Partial discharge defect detection and location
- Switchgear manufacturing plants: Factory type tests and outgoing quality control
- GIS manufacturing plants: On-site commissioning and acceptance tests
- Power engineering companies: Power grid construction and renovation project acceptance
- Industrial and mining enterprises: Internal power equipment routine inspection
Advantages
Compliance with International Standards
Fully meets DL/T 1432.3-2016, DL/T 1982-2019 and IEC 60270:2015 standards → test results are globally recognized
4-in-1 Multi-Sensor Integration
One instrument covers all mainstream partial discharge detection methods → can detect partial discharge of all types of power equipment, no need for multiple instruments
Built-in Expert Diagnosis System
Automatically identifies discharge types and judges severity → reduces operator skill requirements, eliminates subjective judgment errors
Intelligent IoT Inspection Management
RFID equipment identification + wireless data upload → realizes intelligent inspection management and data traceability
Multiple Synchronization Modes
Supports internal, power and optical synchronization → adapts to different on-site test conditions
0.45kg Ultra-Light Handheld Design
One-hand operation, fits in a tool bag → ideal for high-altitude operations and narrow space testing
Long Battery Life
8-hour continuous operation on a single charge → sufficient for a full day of on-site inspections
Strong Anti-Interference Ability
Multi-stage digital filtering + background noise subtraction → obtains reliable test results even in strong electromagnetic environments
FAQ
Q: What is the difference between GDPD-316M and other partial discharge testers?
A: GDPD-316M integrates TEV, AE, UHF and HFCT four mainstream partial discharge detection methods into one unit, which can detect partial discharge of all types of power equipment. It also has built-in expert diagnosis system, RFID equipment identification and IoT functions, making it the most comprehensive handheld partial discharge tester on the market.
Q: Which detection method should I use for different equipment?
A:
- Switchgears and ring main units: TEV + non-contact ultrasonic
- GIS equipment: UHF + contact ultrasonic
- Power transformers: UHF + HFCT (grounding wire) + ultrasonic
- High-voltage cables: HFCT (grounding wire) + ultrasonic (terminals)
Q: Does the test require power outage?
A: No. GDPD-316M is a live detection instrument, which can perform partial discharge detection on operating equipment without power outage, greatly reducing the impact on power supply.
Q: Can it automatically generate test reports?
A: Yes. The instrument can automatically generate standardized Word/PDF test reports with test data, maps and expert diagnosis results, which can be exported via USB or uploaded to the cloud via WIFI.
Q: How long does the battery last?
A: The built-in lithium battery can work continuously for more than 8 hours, which is sufficient for a full day of on-site inspections. The charging time is about 5 hours.