Description

The GDPD-313P/314P is a cost-effective, field-optimized handheld partial discharge detectorexclusively designed for live detection of 10kV-35kV switchgears and ring main units. It fully complies with DL/T 1630-2016, DL/T 1432.3-2016 and IEC 60270:2015 standards, adopting an innovative pistol ergonomic design and integrating TEV transient earth voltage and AE acoustic emission dual detection technologies to achieve non-contact live detection without power outage or climbing.
The instrument is available in two models: GDPD-313P (Basic Type) with built-in TEV and built-in air-coupled ultrasonic sensors, suitable for daily routine inspection; GDPD-314P (Enhanced Type) supports external ultrasonic concentrator, HFCT high-frequency current sensor and UHF ultra-high frequency sensor, which can be extended to detect power cables and GIS equipment. Equipped with a 4.3-inch high-resolution color touch screen, it displays real-time discharge waveform, amplitude and pulse count. The unique three-color early warning system intuitively indicates the defect severity level (green: normal, yellow: attention, red: abnormal). The built-in headphone monitoring function allows operators to distinguish discharge types through auditory characteristics. With a built-in rechargeable lithium battery and ultra-light weight of less than 1kg, it supports one-hand operation and is ideal for all-day on-site inspections. Ideal for power company distribution network inspection, substation switchgear daily maintenance, switchgear factory outgoing inspection and acceptance test.

Specifications

Parameter GDPD-313P (Basic Type) GDPD-314P (Enhanced Type)
TEV Detection
Sensor Type Built-in capacitive coupling Built-in capacitive coupling
Frequency Range 10MHz ~ 100MHz 10MHz ~ 100MHz
Measurement Range 0 ~ 50dB 0 ~ 50dB
Accuracy ±1dB ±1dB
Resolution 1dB 1dB
AE Detection
Sensor Type Built-in air-coupled Built-in/switchable external air-coupled
Resonance Frequency 40kHz ± 1kHz 40kHz ± 1kHz
Measurement Range -10dBuV ~ 70dBuV -10dBuV ~ 70dBuV
Sensitivity -68dB -68dB
Accuracy ±1dB ±1dB
External Ultrasonic Concentrator - Optional (10dB gain, 5m laser positioning)
Optional Sensors
HFCT Sensor - Optional (50kHz~30MHz, 10pC sensitivity)
UHF Sensor - Optional (300MHz~1500MHz, -75dBm~-35dBm)
System Parameters
Display 4.3-inch color TFT LCD capacitive touch screen 4.3-inch color TFT LCD capacitive touch screen
Early Warning System Three-color (green/yellow/red) Three-color (green/yellow/red)
Headphone Output 3.5mm stereo jack 3.5mm stereo jack
Data Storage TF card (up to 32GB) TF card (up to 32GB)
Data Export USB USB
Power Supply
Battery Type Built-in 12V/2500mAh lithium battery Built-in 12V/2500mAh lithium battery
Battery Life ≥4 hours continuous operation ≥4 hours continuous operation
Charging Time ~7 hours (full charge) ~7 hours (full charge)
General Parameters
Dimensions Body: 240×240×80mm, Handle: 146×46.5×40mm Body: 240×240×80mm, Handle: 146×46.5×40mm
Weight <1kg (including battery) <1kg (including battery)
Housing Rugged ABS plastic with rubber protective corners Rugged ABS plastic with rubber protective corners
Operating Temperature -10℃ ~ +50℃ -10℃ ~ +50℃
Operating Humidity ≤90% RH (non-condensing) ≤90% RH (non-condensing)
Altitude ≤2000m ≤2000m
Compliance DL/T 1630-2016, DL/T 1432.3-2016, IEC 60270:2015 DL/T 1630-2016, DL/T 1432.3-2016, IEC 60270:2015

Applications

Core Test Objects

  • Switchgears: 10kV-35kV indoor/outdoor metal-enclosed switchgears
  • Ring main units: 10kV-35kV SF₆-insulated and air-insulated ring main units
  • Cable terminals: High-voltage cable terminals and intermediate joints
  • Distribution transformers: 10kV-35kV dry-type and oil-immersed distribution transformers
  • Other equipment: Reactors, surge arresters, disconnect switches

Typical Usage Scenarios

  • Power companies: Distribution network daily inspection and substation routine maintenance
  • Switchgear manufacturing plants: Factory type tests and outgoing quality control
  • Power engineering companies: Distribution network construction and renovation project acceptance
  • Industrial and mining enterprises: Internal power equipment routine inspection and maintenance
  • Third-party testing institutions: Basic acceptance testing of distribution equipment

Advantages

Compliance with International Standards

Fully meets DL/T 1630-2016, DL/T 1432.3-2016 and IEC 60270:2015 standards → test results are globally recognized

Pistol Ergonomic Design

One-hand operation, no need for climbing or contact → eliminates safety risks of high-altitude operations, greatly improves inspection efficiency

TEV+AE Dual Detection Technology

Covers all main types of switchgear insulation defects → cross-validation reduces false alarms and missed alarms

Dual Model Selection

Basic type for daily inspection, enhanced type for in-depth diagnosis → meets different application needs, cost-effective

Three-Color Early Warning System

Intuitive indication of defect severity → no professional knowledge required, easy for front-line operators to use

FAQ

Q: Does the test require power outage?

A: No. GDPD-313P/314P are live detection instruments, which can perform partial discharge detection on operating equipment without power outage, greatly reducing the impact on power supply.

Q: How to judge the severity of defects?

A: The instrument adopts a three-color early warning system:
  • Green (normal): TEV <20dB, AE <30dBuV, no obvious discharge signal
  • Yellow (attention): TEV 20~30dB, AE 30~40dBuV, weak discharge signal, need to retest within 6 months
  • Red (abnormal): TEV >30dB, AE >40dBuV, strong discharge signal, need to arrange power outage maintenance as soon as possible