GDSL-A-5000A 10V Single-Phase Digital High Current Generator
GDSL-A-5000A Digital Intelligent Single-Phase High Current Generator with 0-5000A Adjustable Output, 10V High Output Voltage, Built-in CT Ratio & Polarity Test Function, for Electrical Equipment Short-Duration High Current Test.
- Description
- Specifications
- Applications
- Advantages
- FAQ
- Recommended Products
Description
The GDSL-A-5000A 10V is a professional-grade, general-purpose single-phase digital high current generatorexclusively designed for short-duration high current tests, current transformer ratio and polarity verification, protection relay calibration and low-voltage circuit breaker testing in power systems, electrical manufacturing and industrial enterprises. It fully complies with GB/T 14048.1-2023, GB 7251.1-2013 and IEC 60947-1:2020 standards, adopting an innovative split modular design that separates the control console and current booster, both equipped with universal wheels and brakes for easy on-site transportation and deployment.
The instrument features a high-efficiency toroidal current booster with low loss and high output efficiency, delivering 0-5000A single-phase continuously adjustable large current output with ±1% measurement accuracy and 0.2% current stability. The 10V high output voltage enables it to drive longer distance high current cables and higher impedance loads, solving the problem of insufficient current output of traditional 6V generators in long-distance test scenarios. The output waveform is a standard sine wave with distortion ≤3%, meeting the strict requirements of international standards for test waveforms. The built-in 0.2-class high-precision true RMS current transformer eliminates the need for external standard meters, ensuring accurate and reliable measurement results.
Specifications
| Parameter | Specification |
|---|---|
| System Parameters | |
| Compliance Standard | GB/T 14048.1-2023, GB 7251.1-2013, IEC 60947-1:2020, DL/T 848.1-2004 |
| Structure Type | Split modular (control console + current booster) |
| Mobility | Universal wheels with brakes on both units |
| Operation Modes | Manual mode / Automatic mode |
| Display | 4.3-inch 480×272 color digital display |
| Parameter Memory | 5 groups of test parameters |
| Timing Function | 0 ~ 999.9s adjustable, ±0.1s accuracy, audible alarm |
| Action Time Measurement | 0 ~ 9999.9ms adjustable, ±0.1ms accuracy |
| Electrical Parameters | |
| Input Power | AC 380V±10%, three-phase four-wire, 50Hz±1Hz |
| Rated Capacity | 50kVA |
| Output Current Range | 0 ~ 5000A AC single-phase continuously adjustable |
| Output Voltage Range | 0 ~ 10V AC continuously adjustable |
| Current Accuracy | ±1% of reading |
| Current Stability | ≤0.2% |
| Current Resolution | 0.1A |
| Output Waveform | Standard sine wave |
| Waveform Distortion | ≤3% |
| Rated Duty Cycle | 5 minutes at 5000A, continuous operation at ≤2500A |
| Special Test Functions | |
| CT Ratio Test | Yes (automatic calculation and display) |
| CT Polarity Test | Yes (automatic judgment and display) |
| Action Time Measurement | Yes (circuit breakers, relays, etc.) |
| Protection Functions | |
| Overcurrent Protection | Yes (adjustable threshold) |
| Overload Protection | Yes (110% rated current) |
| Overheat Protection | Yes (85℃ automatic stop) |
| Short Circuit Protection | Yes (≤1ms response) |
| Zero Position Protection | Yes |
| Emergency Stop | Yes |
| Power Supply | |
| Input Power | AC 380V±10%, three-phase four-wire, 50Hz |
| Power Consumption | ≤50kW (peak) |
| Physical Parameters | |
| Control Console Dimensions | 500×400×350mm (L×W×H) |
| Current Booster Dimensions | 600×500×400mm (L×W×H) |
| Control Console Weight | ~30kg |
| Current Booster Weight | ~60kg |
| Total Weight | ~90kg |
| Housing | Cold-rolled steel with electrostatic spraying |
| Protection Grade | IP40 |
| Operating Temperature | -10℃ ~ +50℃ |
| Storage Temperature | -20℃ ~ +60℃ |
| Humidity | ≤85% RH (non-condensing) |
| Altitude | ≤2000m (customizable for higher altitudes) |
Applications
Core Test Objects
- Instrument Transformers: Current transformers (CT) ratio and polarity test, transformation ratio verification
- Protection Devices: Current relays, thermal relays, overcurrent protectors calibration, action time measurement
- Switchgear: Low-voltage circuit breakers, disconnectors, load switches, fuse switches test
- Busbar & Cable: Short-duration busbar temperature rise test, cable connection resistance test
- Other Equipment: Motor starters, contactors, distribution cabinets inspection
Typical Usage Scenarios
- Power companies: Substation on-site inspection, CT ratio and polarity verification, protection device calibration
- Switchgear manufacturers: Factory quality control, batch production inspection of low-voltage breakers
- Power plants: Generator auxiliary equipment test, low-voltage distribution system inspection
- Industrial enterprises: Internal electrical equipment maintenance, motor protection test
- Third-party testing institutions: Electrical equipment certification testing, on-site calibration services
Advantages
Compliance with Latest International Standards
Fully meets GB/T 14048.1-2023 Chinese national standard, IEC 60947-1 international standard and DL/T 848.1 industry standard → test results are recognized worldwide
Industry-Leading 10V High Output Voltage
Can drive up to 50m long high current cables and higher impedance loads, solving the problem of insufficient current output of traditional 6V generators in long-distance test scenarios → ideal for on-site testing in large substations and industrial plants
Built-in Professional CT Test Functions
Automatic CT ratio and polarity test, action time measurement → one instrument replaces multiple traditional test equipment, greatly improving on-site work efficiency
High-Precision & Stable Current Output
±1% measurement accuracy, 0.2% current stability, true RMS measurement → ensures accurate and reliable test results for all electrical equipment
Intelligent Digital Control
4.3-inch color digital display, dual operation modes, parameter memory function → simple and intuitive operation, reduces operator skill requirements
Comprehensive Multi-Level Safety Protection
Multiple electrical and mechanical protection measures, isolated control circuit → ensures absolute safety of operators and equipment during high current testing
Split Mobile Design
Control console and current booster separated, both with universal wheels, easy to carry and deploy in different test sites → ideal for both factory laboratory and on-site acceptance tests
Industrial-Grade Reliability
Rugged construction, forced air cooling, wide operating temperature range → works reliably in various harsh field environments
FAQ
Q: What is the advantage of 10V output voltage compared to traditional 6V generators?
A: The output voltage of a high current generator determines its ability to drive load impedance. According to Ohm's law (I=V/R), for the same output current, higher voltage can drive higher impedance loads. This means GDSL-A-5000A 10V can:
- Drive up to 50m long high current cables (compared to 20m for 6V generators)
- Test equipment with higher connection resistance
- Provide more stable current output in long-distance test scenarios
- Reduce power loss in cables, improving test efficiency and accuracy
Q: How does the automatic CT ratio and polarity test work?
A: GDSL-A-5000A has a built-in secondary current measurement channel (0~5A). When testing a current transformer:
- Connect the primary side of the CT to the output of the generator
- Connect the secondary side of the CT to the secondary input terminal of the instrument
- Set the rated ratio of the CT in the instrument menu
- Start the test, the instrument will automatically output a stable current
- The instrument will simultaneously measure the primary current and secondary current
- Automatically calculate and display the actual ratio and judge the polarity (positive/negative)
Q: How long can the equipment operate continuously at rated current?
A: GDSL-A-5000A can operate continuously for 5 minutes at 5000A rated current with the built-in forced air cooling system. For currents ≤2500A, it can operate continuously for an unlimited time. For longer duration tests at rated current, we recommend using our GDSL-D series long-duration high current generators.